Alarm Type
For the alarm 1, select alarm types out of the 12 alarm types listed in the following table.
Set Value
0
Alarm function OFF
*1
Upper- and lower-limit (deviation)
1
2
Upper-limit (deviation)
3
Lower-limit (deviation)
*1
Upper- and lower-limit range (deviation)
4
*1
Upper- and lower-limit with standby se-
5
quence (deviation)
6
Upper-limit with standby sequence (de-
viation)
7
Lower-limit with standby sequence (de-
viation)
8
Absolute-value upper-limit
9
Absolute-value lower-limit
10
Absolute-value upper-limit with standby
sequence
11
Absolute-value lower-limit with standby
sequence
*1: With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
"L" and "H."
Following operations are for cases when an alarm set point is "X"
or negative.
*2: Set value: 1, Upper- and lower-limit alarm
Case 1
Case 2
*3: Set value: 4, Upper- and lower-limit range
Case 1
Case 2
L H
4
Digital Temperature Controllers
Alarm Type
Output OFF
Case 3 (Always ON)
=
=
Case 3 (Always OFF)
=
=
E5GN
Alarm Output Operation
When X is positive
*5
*4: Set value: 5, Upper- and lower-limit with standby sequence
Case 1
Case 2
Same as for the upper- and lower-limit
alarm. However, when the upper-limit
and lower-limit hysteresis overlaps:
Always OFF
*5: Set value: 5, Upper- and lower-limit with standby sequence
alarm. Always OFF when the upper-limit and lower-limit hystere-
sis overlaps.
Set the alarm types for alarm 1 and alarm 2 independently in the
initial setting level. The default setting is 2 (upper limit). With the
E5AN/E5EN, perform settings similarly for alarm 3.
Example: When the alarm is set ON at 110°C/°F or higher.
When an alarm type other
than the absolute-value
alarm is selected
(For alarm types 1 to 7)
The alarm value is set as a
deviation from the set point.
Alarm value
Set point
100°C/°F
When X is negative
*2
*3
*4
Example
When the absolute-value
alarm is selected
(For alarm types 8 to 11)
The alarm value is set as
an absolute value from the
alarm value of 0°C/F.
Alarm value
0°C/°F