4. Avoid using the Controller in places near a radio, television set, or
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller.
Mounting
1. Insert the E5GN into the mounting hole in the panel from the
front.
2. Push the adapter along the E5GN body from the terminals up to
the panel, and secure it temporarily.
3. Tighten the two fixing screws on the adapter. When tightening
screws, tighten the two screws alternately keeping the torque to
within approximately 0.29 to 0.39 N·m.
Removing and Attaching the Terminal Plate
The E5GN can be replaced by removing the terminal plate.
1. Press down hard on the fasteners on both sides of the terminals
to unlock the terminal plate and pull upwards.
2. Draw out the terminal plate as it is.
3. Before you insert the terminal plate again, make sure that the pins
match the positions of the holes in the terminal plate.
18
Digital Temperature Controllers
Adapter
Waterproof packing
Panel
E5GN
Wiring Precautions
• Connect the terminals as specified below.
Terminal No.
1 to 6
AWG24 to AWG14
7 to 9
AWG28 to AWG22
• The exposed current-carrying part to be inserted into terminals
must be 5 to 6 mm.
5 to 6 mm
Electrical wire
• Tighten the terminal screws to the torque specified below.
Terminal No.
Screw
1 to 6
M2.6
7 to 9
M2
Cables
Pin terminals
2.1 dia. max.
1.3 dia. max.
5 to 6 mm
Pin terminal
Maximum tightening
torque
0.23 to 0.25 N·m
0.12 to 0.14 N·m