Input Shift
All points in the sensor range are shifted by the value set as the tem-
perature input shift value.
Example
Input shift setting
Temperature
measured by
sensor
100 ° C
0 (no shift)
10 (shifted +10 ° C)
100 ° C
− 10 (shifted − 10 ° C) 100 ° C
Protect Level
Operation/adjustment protection
oapt
Restricts displaying and modifying menus in operation,
0
adjustment, and manual control levels.
Initial setting/communications protection
icpt
1
This protect level restricts movement to the initial setting,
communications setting, and advanced function setting
levels.
Setting change protection
wtpt
off
Protects changes to setups by operating the front panel
keys.
Operation/Adjustment Protection
The following table shows the relationship between set values and
the range of protection.
Level
Operation level
PV
PV/SP
Other
Adjustment level
When this parameter is set to "0," parameters are not protected.
Default setting: 0
:
Can be displayed and changed
: Can be displayed
X : Cannot be displayed and move to other levels not possible
Initial Setting/Communications Protection
This protect level restricts movement to the initial setting level, com-
munications setting level and advanced function setting level.
Set
Initial setting level Communication
value
0
1
2
X
Default setting: 1
: Move to other levels possible
X: Move to other levels not possible
14
Digital Temperature Controllers
Temperature
display
100 ° C
110 ° C
90 ° C
Set value
0
1
2
X
X
X
Advanced
s setting level
function setting
level
X
X
X
E5GN
Setting Change Protection
This protect level protects setup from being changed by operating
the keys on the front panel.
Set value
OFF
ON
Default setting: OFF
3
X
X
Description
Setup can be changed by key operation.
Setup cannot be changed by key operation.
(The protect level, can be changed.)