Specification Setting after Turning ON Power
Initial Setting Level
This level is used for setting basic specifications of the Temperature
Controller. Using this level, set the input type for selecting the input to
be connected such as the thermocouple or platinum resistance ther-
mometer and set the range of set point and the alarm mode.
Power ON
Operation level
Adjustment level
key
Less than 1 second
key
key
25
3 seconds
100
1 second min.
min.
Initial setting
level
key
Less than 1 second
key
Password input
1 second min.
set value "−169"
Advanced function
setting level
Password input
set value "1201"
Calibration level
The move from the operation level to the initial setting level, press
key for three seconds or more.
The initial setting level is not displayed when "initial/communications
protection" is set to "2." This initial setting level can be used when
"initial setting/communications protection" is set to "0" or "1."
The "scaling upper limit," "scaling lower limit," and "decimal point"
parameters are displayed when an analog voltage input is selected
as the input type.
10
Digital Temperature Controllers
key
+
Display flashes
when key pressed.
+
key
25
100
1 second min.
+
Control stops.
3 seconds
min.
Communica-
tions setting
level
Protect level
The time taken to move
to the protect level can
be adjusted by changing
the "Move to protect lev-
el time" setting.
Control in progress
Control stopped
Level change
E5GN
Initial Setting Level
Input type
in-t
0
Scaling upper limit
in-h
100
Scaling lower limit
in-l
0
key
Decimal point
dp
0
Temperature unit
d-u
°C, °F
c
SP upper limit
c
sl-h
1300
Limit the set point.
SP lower limit
c
sl-l
-200
PID ON/OFF
cntl
onof
Standard or
s-hc
heating/cooling
stnd
ST
st
on
For input type of temperature,
standard, or PID
Control period (heating)
cp
20
Set the pulse output cycle.
Control period (cooling)
c-cp
20
Direct/reverse operation
ore?
or-r
Alarm 1 type
alt1
2
Move to advanced
amo?
function setting level
0
Displayed when initial setting/
communications protection is set to 0
To return to the operation level, press the
second.
key for longer than one