Samsung AF HV Series User & Installation Manual page 49

Table of Contents

Advertisement

4. Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.
- The compression dimension should be 8.0.
- After compressing it, pull both sides of the wire to make sure it is firmly pressed.
Compression
dimension
5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
Three or more layers of insulation are required.
Method 1
Insulation tape
40 mm
6. Apply heat to the contraction tube to contract it.
7. After tube contraction work is completed, wrap it with the insulation tape to
finish.
• Make sure that the connection parts are not exposed to outside.
• Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials
CAUTION
that have the same level of withstand voltage with the power cable. (Comply with the local regulations on
extensions.)
• In case of extending the electric wire, please DO NOT use a round-shaped pressing socket.
- Incomplete wire connections can cause electric shock or a fire.
WARNING
Method 1
Compress it 4 times.
5 mm
Method 2
Insulation tape
35 mm
ENGLISH-49
Method 2
Compress it 4 times.
5 mm
Contraction tube
Insulation tape