Pellet boiler
TECHNICAL PASSPORT
INSTALLATION AND MAINTENANCE MANUAL

Advertisement

loading

Summary of Contents for Stropuva Pellet boiler Series

  • Page 1 Pellet boiler TECHNICAL PASSPORT INSTALLATION AND MAINTENANCE MANUAL...
  • Page 2 Stropuva “Granulinis” is steel boiler with automatic pellet feed (without helical conveyer), fired using 6 mm – 8 mm wood pellets. They are designed for heating of apartments, premises, small shops, repair shops. Temperature of water in boiler is 85 C and highest pressure of heat transfer medium is –...
  • Page 3 • Regulations and standards related to safety of related technical equipment and hydraulic heating systems. __________________________________________________________________________________________________ Use only original STROPUVA parts. STROPUVA cannot be held responsible for damage done by using other manufacturer’s parts. __________________________________________________________________________________________________ DANGER Danger of poisoning with carbon monoxide.
  • Page 4 DANGER Flammable materials or liquids may catch fire. It is forbidden to store flammable materials and liquids near the boiler. • • Respect the indication of minimum distance between boiler and easily flammable materials. 1.5. Advice for user ATTENTION! • Boiler can only be operated by adults who are familiar with boiler’s manual.
  • Page 5 1.6. Minimum distance and flammability of materials Different countries may have different minimum distances than indicated further. You can ask installer or chimney sweep for information about it. • Minimum distance from wall of boiler and chimney to material of average flammability must be at least 600 Minimum distance from flammable materials must be at least 200 mm.
  • Page 6: Description Of Product

    Simple domestic tools like scoop, broom and shovel can be used for maintenance of boiler. To clean the boiler you will need brush, poker and scraper, ash pump. 2. DESCRIPTION OF PRODUCT 2.1 General information Pay attention to the instructions for connecting the boiler to heating system. Installation of boiler must be carried out in accordance with rules and standards that apply for heating systems in that country, especially: •...
  • Page 7 2.2 Pellet boiler Boiler for heating water in the system. Highest temperature of outgoing water is 85 C, and allowed operational pressure at lowest point of heating system – 1,5 bar. Technical data is presented in additional table and instructions can be found in rated data plate.
  • Page 8 2.3 Pellet burner • Burner – for burning and feeding fuel. Burning chamber is cube shaped – it is attached to the housing of boiler. It is used to put in a burner and to burn • fuel. • Fuel bunker (5.) – attached over the burning chamber and it is used to hold fuel. •...
  • Page 9: Technical Data

    3. TECHNICAL DATA Parameter Measuring “Pellet boiler” with “Pellet boiler” “Pellet boiler” unit 30 kg hopper with 60 kg with 90 kg hopper hopper Rated power Heated area [1] Up to 200 Up to 200 Up to 200 Efficiency Width Length 1000 Height...
  • Page 10 4. CHIMNEY Chimney of appropriate height and diameter is very important for proper operation of boiler. Before connecting the boiler to the chimney, check if its flue is suitable (diameter of flue must be not lower than of boiler’s flue), if there are other systems connected to the chimney.
  • Page 11: Connection To Hydraulic System

    5. CONNECTION TO HYDRAULIC SYSTEM 5.1. Installation in closed system According to requirements of this manual, boiler is allowed to be used in closed system only after installing specific safety devices. On our boiler (on back side, near the flue) there is ½ inch connection for protection system. Manufacturer does not take responsibility for quality, selection and appropriate installation of devices for protection from higher temperature than 95 C and higher pressure than 1,5 bar.
  • Page 12 7.2 Ignition Before igniting the boiler – fuel bunker must be filled up, controller must be connected to power supply and boiler’s temperature must be set in contact thermostat (recommended 0 Boiler has ignition, observation opening, which when opened – allows to light the fuel with use of gad lighter. First ignitions must be carried out mechanically.
  • Page 13 electronics lovers, it is possible to use sophisticated room thermostats remotely controlled, even by computer or mobile phone. I would like to use such devices, follow their instructions. 3. Wiring room thermostat connector. A trumpet was killed by using another set of shirts, a cord, a room thermostat. Room thermostats can be connected directly to the terminals in the box.
  • Page 14 Attention! When device is in operation, cover of tank must be fully closed. Attention! In order to fill fuel tank with pellets, contact thermostat must be set to zero and fan must be turned off. If fuel meets the standards and recommendation of manufacturer, ash will fall into ash chamber. If fuel doesn’t meet the standards, requirements and manufacturer’s instructions, there can be malfunctions of burning process, buildup of condensate, soot and resin.
  • Page 15 7.8. Accidental combustion of sooth in chimney Sooth in dirty chimney can flame up. This can cause fire of all house or nearby houses and walls of the chimney can start to shatter. In case of combustion of sooth a chimney it is important to: •...
  • Page 18 7.11 Rules of safe operation Boiler’s equipment can be operated safely when the requirements of Country in which it is operated. Also, follow these instructions when using the boiler: 1. These actions have to be carried out before doing any maintenance work: a) Turn of the fan or switch it to STOP mode without air flow (set the contact thermostat to 0...
  • Page 19: Environmental Protection

    b) Use up the remaining pellets in the bunker. 2. All maintenance works must be carried out while wearing gloves, protective glasses and helmet. a) Boiler room must be well ventilated when cleaning the boiler. b) Do not use the boiler if level heat exchanger medium in the system is lower than indicated in boiler room operation manual.
  • Page 20 UAB “STROPUVA IR KO” cannot be held responsible for indirect losses or damage, which is caused by additional inconveniences because of inability to use the device or its parts, which are under warranty. Client’s complaints about damages, other than damages caused after delivery of good because of physical defects, are not accepted.
  • Page 21 10. Warranty application For general director of UAB “STROPUVA IR KO” A …………………………………………………………………………, I purchased a product which was manufactured in your company. (name, surname and company’s name) product:…………………………………………………………………, manufacture No………………………………………………………………………………. (products name) (date of manufacture) ………………………………………………………………………………………………………………………………………………………………………………………….. (place, date of purchase, name and number of purchase documents) After studying product’s technical passport, I declare that product was installed according to requirements presented in...
  • Page 22 10.1. Boiler’s passport Boiler’s passport must be filled out thoroughly. If passport is not filled out, warranty does not apply. In case of failure of device, copy of this passport is sent to seller or distributor. Original copy of passport must be presented to authorized technician who comes to repair the failure.