Omron NX Series User Manual page 70

Machine automation controller system units
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

4 Installation and Wiring
The following are wiring diagrams (examples) for each power supply.
Communications Coupler Unit
Unit power supply
terminals
I/O power
supply
Unit
power supply
(24 VDC)
Precautions for Correct Use
Always use separate power supplies for the Unit power supply and the I/O power supply. If
you supply power from the same power supply, noise may cause malfunctions.
Additional Information
Refer to the user's manual for the Communications Coupler Unit on design for power supply
to the Slave Terminal.
4 - 10
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
(Example) DC Input Unit
24 VDC I/O
power supply
Additional I/O
Power Supply Unit
A1
IOV
IOG
IOV
IOG
A8
NX Unit
Internal power
supply circuit
I/O power supply terminals
To external
devices
24 VDC Unit
power supply
Additional
DC Input Unit
NX Unit Power
Supply Unit
B1
A1
B1
A1
IOV
UV
UV
UG
UG
IOG
NC
IOV
NC
IOG
B8
A8
B8
A8
NX Unit
Additional NX Unit
power supply
Power Supply Unit
The I/O power supply is
separated.
To external
devices
I/O
External
External
power
output
output
supply
device
device
I/O power supply (Supply from external source)
NX-series System Unit User's Manual (W523)
Two-wire
sensor
B1
0
1
IOV
IOV
Three-wire
IOG
IOG
sensor
2
3
IOV
IOV
IOG IOG
B8
NX Unit
power supply
The I/O power
supply is not
separated.
End Cover
Additional
I/O Power
To external
Supply
devices
Unit

Advertisement