Installation orientation
and restrictions
Terminal connection dia-
gram
*1. You can use the unwired terminals of the Unit power supply terminals (UV/UG) for through-wiring of the Additional NX
Unit Power Supply Unit or the Unit power supply terminals on the EtherCAT Coupler Unit.
*2. The NC terminals are not connected to the internal circuits.
NX-series System Unit User's Manual (W523)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Installation orientation: Possible in 6 orientations.
Restrictions:
• For upright installation
Output power (W)
12
10
8
6
4
2
0
0
10
Ambient operating temperature (°C)
• For any installation other than upright
Output power (W)
12
10
8
6
4
2
0
0
10
Ambient operating temperature (°C)
24 VDC Unit
power supply
Ground of 100 Ω
or less
For 10 W output, 40°C
20
30
40
45
50
55
For 10 W output, 40°C
20
30
40
45
50
55
Additional NX Unit
Power Supply Unit
NX-PD1000
A1
B1
UV
UV
UG
UG
*2
*2
NC
NC
A8
B8
Appendices
For 8.5 W output, 55°C
60
For 6.0 W output, 55°C
60
Through-wiring for unwired terminals
A
*1
A - 5