Horizontal Airflow (Rz25/35/42Vk); Side View (Inner Vane); Side View (Outer Vane) - Panasonic CS-RZ25VKRW Service Manual

Indoor/outdoor units
Hide thumbs Also See for CS-RZ25VKRW:
Table of Contents

Advertisement

2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
Reference point
Reference point
* The horizontal vane angle tolerance is within +/- 5 degree.
14.4.2

Horizontal Airflow (RZ25/35/42VK)

The horizontal airflow direction louver can be adjusted manually by hand.
58°C
36°C
Indoor Heat
Exchanger Temperature
Step 1
Step 2
Step 3
Step 4
Closed
Stopper
Position
Step 1
Step 2
Step 3
C
50°C
B
30°C
A
Figure 1

Side View (Inner Vane)

110° (RZ25/35/42VK)
148° (RZ50/60/71/80VK)
Step 5

Side View (Outer Vane)

Step 4
Step 5
Figure 2
102
Stopper
Closed
Position
135° (RZ25/35/42VK)
101° (RZ50/60/71/80VK)