16.3.3

Overload Protection Control

The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown
below.
If the heat exchanger temperature exceeds 60°C, compressor will stop.
16.3.4

Low Temperature Compressor Oil Return Control

In heating operation, if the outdoor temperature falls below -10°C (RZ25 ~ 35VK), -8°C (RZ42 ~ 80VK) when
compressor starts, the compressor frequency will be regulated up to 600 seconds.
16.3.5

Cold Draught Prevention Control

When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
16.3.6

Deice Operation

When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor
and outdoor fan motor stop and operation LED blinks.
OFF
60°C
Frequency Reduce
55°C
Frequency Limited
49°C
Free
Indoor Heat
Exchanger Temp.
113
52°C
46°C