12.3 Select the Best Location

12.3.1
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Table A
Piping size
Capacity
Model
W
Gas
(HP)
RZ25*** 1.0HP
9.52 mm
"
(3/8
)
RZ35***
1.5HP
RZ42*** 1.75HP
12.7 mm
RZ50***
2.0HP
6.35 mm
"
(1/2
)
RZ60*** 2.25HP
RZ71*** 2.5HP
15.88 mm
"
(5/8
)
RZ80***
3.0HP
(*) Systems with total refrigerant charge, m
Example: For RZ25***
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m × 10 g/m =
25 g.
A
= (m
/ (2.5 × (LFL)
min
c
A
= Required minimum room area, in m
min
m
= Refrigerant charge in appliance, in kg
c
LFL
= Lower flammability limit (0.307 kg/m
h
= Installation height of the appliance (1.8 m for wall mounted)
0
SF
= Safety factor with a value of 0.75
** The required minimum room area, A
A
= m
min
c
The higher value shall be taken when determining the room area.
Min.
Std.
Max
Piping
Length
Elevation
Length
Liquid
(m)
(m)
(m)
15
3
15
3
15
3
15
3
5
"
(1/4
)
15
3
20
3
20
3
lower than 1.84kg are not subjected to any room area requirements.
c
(5/4)
2
× h
))
0
2
3
)
, shall also be governed by the safety factor margin formula below :
min
/ (SF × LFL × h
)
0
It is advisable to avoid more
than 2 blockage directions.
For better ventilation &
multiple-outdoor installation,
please consult authorized
dealer/specialist.
This illustration is for explanation purposes only.
Max.
Piping
Additional
Piping
Length for
Refrigerant
Length
add. gas
(g/m)
(m)
(m)
20
10
7.5
20
10
7.5
20
10
7.5
30
15
10
30
15
10
30
25
10
30
25
10
** not less than safety factor margin
68
Max.
Refrigerant
Indoor
2
Charge
A
(m
)
min
(kg)
0.80
Not applicable (*)
0.98
Not applicable (*)
1.00
Not applicable (*)
1.44
Not applicable (*)
1.52
Not applicable (*)
1.82
Not applicable (*)
1.99
4.80
Power supply cable ( )
Connection cable ( )
1/4" Liquid side piping ( )
Gas side piping ( )
Additional drain
hose ( )
Installation parts you
should purchase ( )

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents