Exchange the drain hose and
the cap
Rear view for left piping installation
Drain hose
Drain cap
How to pull the piping and drain hose out, in case of the
embedded piping.
Apply putty or
caulking material
to seal the wall
opening.
PVC tube for
drain hose (VP-20)
PVC tube for
drain hose
12.2.4

Connect the Cable to the Indoor Unit

1
The inside and outside connection cable can be connected without removing the front grille.
2
Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
2
4 × 1.5 mm
flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short. Allowable connection
cable length of each indoor unit shall be 30 m or less.
3
Bind all the indoor and outdoor connection cable with tape and route the connection cable via the
escapement.
4
Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the
diagram below.
Drain hose
Connection cable
Adjust the piping slightly
downwards.
Connection cable
Piping
Drain hose
from main unit
PVC tube (VP-65) for piping and
connection cable
PVC tube for drain hose (VP-30)
Cable
Piping
Indoor unit
55mm (1/2 ~ 1.75HP) or
82mm (2.0 ~ 3.0HP)
Piping
Drain hose
Sleeve for piping hole
In case of left piping how to insert the
connection cable and drain hose.
Drain hose
(For the right piping, follow the same procedure)
63
Connection cable
More than 950mm
(1/2 ~ 1.75HP) or
1150mm (2.0 ~ 3.0HP)
Cable
Piping