Service Code Detection System
The generator may have to run for long periods of time
with no operator present. For that reason, the system
is equipped with sensors that automatically shut down
the generator in the event of potentially damaging
conditions, such as low oil pressure, high temperature,
over speed, and other conditions. Refer to Service
Code Detection System in the operator's manual for
more detailed information.

Final Installation Considerations

Engine Oil
NOTICE Any attempt to crank or start the engine
before it has been properly serviced with the
recommended oil will result in equipment failure.
• Refer to Maintenance in the operator's manual for oil
fill information.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
The engine is shipped from the factory pre-run and
filled with synthetic oil (API SJ/CF 5W-30). This allows
for system operation in a wide range of temperature
and climate conditions. Before starting the engine,
check oil level and ensure that engine is serviced as
described in Maintenance of the Operator's Manual.
The use of synthetic oil does not alter the required oil
change intervals described in the Operator's Manual.
For operation of temperatures below 30°F (-1°C), the
use of fully synthetic oil (minimum API SJ) of viscosity
5W30 is required.
28
Battery
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
The installer must supply and install a 12 Volt DC
rechargeable starting battery. The starting battery
MUST conform to the specifications shown below in
the chart.
Battery
Standard
Specifications
Volts
12 Volt DC
Amps (MIN)
540 CCA (cold
cranking amps)
Construction
Wet lead acid
Terminal Type
Top post type
battery
Dimensions
BCI size 26
(MAX):
Install the battery as described in Servicing the Battery in
the Maintenance section of the Operator's Manual. Always
make sure the NEGATIVE cable is connected last.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion, resulting in
death, serious injury and/or property damage. Battery
electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe
chemical burns. A battery presents a risk of electrical shock
and high short circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber
boots and rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.
Cold Start
(less than
30°F)
12 Volt DC
630 CCA
(cold cranking
amps)
Wet lead acid
Top post type
battery
BCI size 75