Exhaust Fan Operation

To start the optional power exhaust fans, use the
economizer test procedures in
to drive the economizer dampers to the open position.
The exhaust fans will start when the damper position is
equal to or greater than the exhaust fan setpoint. If
optional power exhaust is selected, an access door
must be field-installed on the horizontal return
ductwork to provide access to exhaust fan motors.
The exhaust fan will start anytime the economizer
damper position is equal to or greater than the exhaust
fan setpoint.
W W A A R R N N I I N N G G
R R o o t t a a t t i i n n g g C C o o m m p p o o n n e e n n t t s s ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n r r o o t t a a t t i i n n g g c c o o m m p p o o n n e e n n t t s s c c u u t t t t i i n n g g a a n n d d s s l l a a s s h h i i n n g g
t t e e c c h h n n i i c c i i a a n n w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s
i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . .
Verify that the fans are operating properly and the CFM
is within the job specifications. Refer to power exhaust
fan performance tables beginning with
for the exhaust fan performance characteristics.
Available power adjustments:
The power exhaust fan(s) comes on based on the
position of the of the exhaust fan setpoint
potentiometer on the RTOM (Reliatel Options
Module). The setpoint is factory set at 25%. The
exhaust fan(s) will come on anytime the
economizer damper position is equal to or greater
than the active exhaust fan setpoint.
Physical damper blade stops limit the amount of
exhaust airflow by limiting the maximum opening
of the damper blades. These stops (sliding brackets
secured with wing-nuts) are present under the rain
hood on the non-modulating power exhaust option.
There is one stop on each side of each damper. The
practical range of blade position control is between
1.5" and 4.0" blade opening. The damper is wide-
open at 4.0". The stops on each side of a damper
must be in the same position, such that the damper
blade connecting member contacts the stops at the
same time.
The modulating power exhaust actuator tracks the
position of the economizer damper actuator such
that the power exhaust dampers proportionally
follow or track the fresh air damper position.
When the Statitrac option is selected, the exhaust
actuator will operate independently of the
economizer in order to relieve positive building
pressure. If a Space Pressure Transducer failure
RT-SVX34R-EN
, p. 68
-
Table 46, p. 74
Table 53, p. 83
occurs, the unit will revert back to fresh air tracking
control.
The proportional offset between the dampers is
adjustable. With direct-drive ultra-low-leak exhaust
options, actuator stroke can be adjusted as
described in
"Economizer (O/A) Dampers," p.
The stroke limit can be set between 33% and 100%
of full stroke.
N N o o t t e e : : The barometric damper continues to function as
a pressure relief damper up to the maximum
stop position.
To adjust the damper blade stops, refer to figure
, p. 83
to
Figure 57, p.
If the fan speed needs to be changed from the current
operating speed, refer to the unit wiring diagram and
the XTB1 and XTB2 terminal strip located in the
economizer section.
Table 53. Power exhaust fan performance— 27.5-35
Ton — 60 Hz
Power Exhaust Selection
50% (min)
Damper Blade Open Distance (in.)
Return
(min)
Duct Static
(in. wc)
0.0
3812
0.1
3497
0.2
3190
0.3
2884
0.4
2621
0.5
2342
Table 54. Power exhaust fan performance — 40-50
Ton — 60 Hz
Power Exhaust Selection
50% (min)
Damper Blade Open Distance (in.)
Return Duct
(min)
Static (in.
wc)
0.0
4854
0.1
4575
0.2
4262
0.3
4011
0.4
3718
0.5
3467
S S t t a a r r t t u u p p
84.
84.
100% (max)
(max)
(min)
(max)
CFM
6866
7624
13742
5296
6995
10591
4458
6325
9000
3812
5768
7635
3359
5241
6719
2885
4683
5771
100% (max)
(max)
(min)
(max)
CFM
8035
9708
16069
7410
9151
14820
6450
8552
13496
6027
8021
12054
5526
7436
11051
5186
6933
10373
83