[ VII Microprocessor Control ]
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Dry thermo
ON
OFF
Remote controller setting is not acceptable.
3. Drain pump
(1) Same control as COOL operation

3. Fan operation

1. Fan
(1) Set by remote controller.
Type
3 speeds + Auto type
When [Auto] is set, fan speed becomes [Low].
2. Drain pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water: Detected that the float switch is ON for 15 seconds.
In the air: Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
HWE1833B
Excluding the following
Room temp. < 64°F
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the [F4] button to display Fan.
15sec.
15sec.
15sec. 1min.30sec.
In the water
In the air
- 13 -
Fan speed notch
[Low]
Fan speed notch
[Low], [Med], [High], [Auto]
1min.30sec.
Drain pump
In the water
Error
postponement
abnormal
Stop
[Low]
GB

Advertisement