Table 80. Component failure mode (continued)
COMPONENT
HSP and CSP for CV or SZ VAV
are both lost.
(ZTEMP) Zone Temperature
Sensor CV, SZ VAV, or VAV
during Unoccupied mode.
TC01, TCO2, TC03 High Temp
Limit
(LPC1) Low Pressure Control
(LPC2) Low Pressure Control
Dual Circuits Only
(CCB1)
(CCB2 or CCB3) Compressor
Overload
(HPC1) High Pressure Control
(HPC2) High Pressure Control
(WTL1) Winding Temperature
Limit
(WTL2 or WTL3) Winding
Temperature Limit
(CC1) Compressor Contactor
24 VAC coil
(CC2 or CC3) Compressor
Contactor 24 VAC coil
(CFS) Clogged Filter Switch
(FFS) Supply Fan Proving
Switch
(SPT) Static Pressure
Transducer VAV
Condensate Overflow Switch
Traq - CFM Setpoint and
airflow sensor
Traq - w/DCV loss of CO2
sensor or CO2 setpoint(s)
RT-SVX34R-EN
FAILURE RESPONSE
Cannot control at ZSM, unit
using RTRM Default Mode.
No Heating or Cooling ZSM
"Fan" selection switch
operates IDM during
Unoccupied Mode.
Heat goes off, IDM runs
continuously.
Compressor CPR1 will not
operate.
Compressor CPR2 will not
operate.
Compressor CPR1 will not
operate.
Compressor CPR2 or CPR3 will
not operate.
Compressor CPR1 will not
operate.
Compressor CPR2 or CPR3 will
not operate.
Compressor CPR1 will not
operate.
Compressor CPR2 or CPR3 will
not operate.
Compressor CPR1 will not
operate.
Compressor CPR2 or CPR3 will
not operate.
This input is for "indication"
only and does not effect the
normal operation of the unit.
Unit will not operate in any
mode.
Fan speed command remains
at 0%.
Closed - Unit will not operate
1. In the event a required Traq
control input is out of range
the Traq Minimum Position
Request will be disabled and a
static value of 10% will be
utilized for minimum position
at all times.
2. If BAS is in "remote control"
and sending a valid OA
Minimum Position Setpoint
that setpoint will be used for
OA Minimum Position,
however a diagnostic
indication will continue to be
set via the BAS and the 2-
blink code will be initiated on
the RTRM to indicate a
problem.
In the event of the loss of a
required control parameter for
DCV when paired with Traq
control the system will revert
to using on the Design
Minimum OA CFM Setpoint
and continue Traq control
functionality without DCV.
NORMAL RANGE
100 to 900 Ohms approx. Use
ZSM Test Procedures.
-40 TO 150 F, 346K to 2.1K
Normally Closed, Open 135 F,
Reset 105 F.
Open 25 PSIG, Close 41 PSIG.
Open 25 PSIG, Close 41 PSIG.
Normally Closed. range varies
by unit.
Normally Closed. range varies
by unit.
Open 650 psig, Close 550 psig
Open 650 psig, Close 550 psig
Normally Closed
Normally Closed
Varies by unit
Varies by unit
"Normal operation = 0 VAC
measured between terminals
J5-1 and Ground.
0.5" W.C. Normally Open
0.25 - 4 Vdc between J8 and
J9 on VAV
N/A
0 to 20000CFM
0 to 2500
DIAGNOSTIC
If a sensor is used at RTRM J6-1 and J6-2,
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED Blinks at ZSM. If RTRM senses
a zone temp input and then it is lost,
CV Cool Failure Output at RTRM J6-8 to J6-
6 "COOL" LED Blinks at ZSM
Heat Failure Output at RTRM J6-7 to J6-6
"HEAT" LED Blinks at ZSM.
Possible Cool Failure at RTRM J1-8 to
Ground, 0 VAC. "COOL" LED Blinks at ZSM.
Possible Cool Failure at RTRM J3-2 to
Ground, 0 VAC. "COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
Cool Failure Output at RTRM J6-8 to J6-6
"COOL" LED blinks at ZSM.
SERVICE LED ON 2-30 Vdc present at
RTRM J6-6 and J6-10.
Service Failure Output at RTRM J6-6 to J6-
10 "SERVICE" LED blinks at ZSM.
Heat and Cool Failure Output at RTRM J6-7
to J6-6 & RTRM J6-8 to J6-6 "HEAT" and
"COOL" LED's blink at ZSM.
Check to make sure the float position is not
in a tripped condition and verify an "open"
between wires connecting to RTOM J6-1,
J6-2.
A diagnostic will be set via BAS
communication and the 2-blink code will be
initiated on the RTRM to indicate a
problem.
The proper failure code will be set on the
RTEM and an indication of the failure will be
set via the BAS Communication packet.
D D i i a a g g n n o o s s t t i i c c s s
141