SETUP AND PROCEDURES BEFORE OPERATION
4 - 8
(2)
Operating procedure
Start the settings with GX Developer I/O assignment setting dialog box.
(a)
I/O assignment setting screen
Set the following for the slot in which the D/A converter module is mounted.
The type setting is required; set other items as needed.
Type
Model name : Enter the module model name.
Points
Start XY
Detailed setting:
1) When using in the standard system configuration (on the main or
extension base), specify the control CPU of the Q62DA-FG.
The analog output status when an error has occurred on the Q62DA-FG
varies depending on the "HOLD/CLEAR function" setting of the switch
setting for intelligent function module. And a value set to "Error time
output mode" is invalid.
2) When using on a remote I/O station, if the analog output is to be held in
the case of a link error, "Error time output mode" must be set to "Hold".
: Select "intelli."
: Select 16 points.
: Enter the start I/O number for the Q62DA-FG.
MELSEC-Q
4 - 8