3.4.10 Output monitor value (buffer memory address 38, 39: Un\G38, Un\G39)

3.4.11 Rate control enable/disable setting (buffer memory address 46: Un\G46)

3 - 32
(1)
The analog value being output is always reconverted into a digital value within
the Q62DA-FG and the result is stored. (Refer to Section 3.2.3.)
Output range setting
0 to 20 mA
4 to 20 mA
User range setting 1
1 to 5 V
0 to 5 V
–10 to 10 V
4 to 20 mA (Extended mode)
1 to 5 V (Extended mode)
User range setting 2
User range setting 3
(2)
Turning on Operating condition setting request (Y9) clears the output monitor
value.
(1)
Set whether to enable or disable the rate control on each channel. (Refer to
Section 3.2.5.)
(2)
To validate a value set to Rate control enable/disable setting, turn on and off
Operating condition setting request (Y9). (Refer to Section 3.3.2.)
(3)
The default setting is all-channel rate control disable.
b15 b14 b13 b12 b11 b10
Un\G46
0
0
b9
0
0
0
0
0
b2 to b15 information is fixed at 0.
Output monitor value
0 to 12000
–16000 to 16000
–3000 to 13500
–12000 to 12000
0 to 12000
b8
b7
b6
b5
b4
0
0
0
0
0
1: Rate control disable
0: Rate control enable
MELSEC-Q
b3
b2
b1
b0
0
0
CH2 CH1
3 - 32