Mitsubishi Electric MELSEC Q Series User Manual page 4

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

[Installation Precautions]
Use the programmable controller in an environment that meets the general specifications
contained in the user's manual of the CPU module to use.
Using this programmable controller in an environment outside the range of the general
specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the
product.
While pressing the installation lever at the bottom of module, insert the module fixing tab into the
fixing hole in the base unit until it stops.
Improper installation may result in malfunction, breakdown or the module coming loose and
dropping.
Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting
or removing the module.
Not doing so may cause damage to the module.
In the system where a CPU module supporting Online module change is used and on the
MELSECNET/H remote I/O stations, modules can be replaced online (during energizing).
However, there are some restrictions on replaceable modules and the replacement procedures
are predetermined for each module.
For details, refer to the chapter of Online module change in this manual.
Do not directly touch the conductive area or electronic components of the module.
Doing so may cause malfunction or failure in the module.
[Wiring Precautions]
After wiring, attach the included terminal cover to the module before turning it on for operation.
Failure to do so may result in electric shock.
Individually ground the FG terminal of the programmable controller with a ground resistance of
100Ω or less.
There is a risk of electric shock or malfunction.
Use applicable solderless terminals and tighten them with the specified torque.If any solderless
spade terminal is used, it may be disconnected when the terminal screw comes loose, resulting
in failure.
Tighten the terminal screws within the specified torque range.
Undertightening can cause short circuit, fire, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
A - 2
CAUTION
!
WARNING
!
CAUTION
!
A - 2

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Q62da-fgGx configurator-daSw2d5c-qdau-e

Table of Contents