Fx 2N -48Er-Ua1/Ul; Product Specifications - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
15.8
FX
-48ER-UA1/UL
2N

15.8.1 Product specifications

The generic specifications are the same as those for the main unit.
For external wiring, refer to the following chapters.
1. Power supply specifications
2. Input specifications (100V AC Input)
Item
Input points
Connection type
Input form
Input signal voltage
Input signal current
Input impedance
Input ON current
Input response
time
Input OFF current
Input response time
Input signal form
Input circuit insulation
Indication of input operation
Input circuit diagram
→ Refer to Section 4.1 for generic specifications.
→ Refer to Chapter 9 for power supply wiring.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
→ For the power supply specifications, refer to Section 15.2.
FX
-48ER-UA1/UL
2N
24 points
Removable terminal block (M3 screw)
AC input
100 to 120V AC +10%,-15% 50/60 Hz
4.7 mA/100V AC 50 Hz (70% or less when turned on simultaneously)
6.2 mA/110V AC 60 Hz (70% or less when turned on simultaneously)
Approx. 21 k /50 Hz
Approx. 18 k /60 Hz
3.8mA or more/80V AC
1.7mA or less/30V AC
Approx. 25 to 30ms
Contact input
Photo-coupler insulation
LED on panel lights when input.
*1
15 Input/Output Powered Extension Units
15.8 FX2N-48ER-UA1/UL
Fuse
L
N
100 to 240V AC
COM
X
*1 Input impedance
11
12
13
14
15
16
17
18
19
20
245