3. Output specifications (relay output type)
Item
Output Points
Connection type
Output unit
External power supply
Output circuit insulation
Indication of output operation
Max. load
Open circuit leakage current
Min. load
Response time
Output circuit configuration

15.3.2 External dimensions

FX
-32ER-ES/UL
2N
2- 4.5 mounting holes
140 (5.52") (mounting hole pitch)
232
240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
The total load current per common terminal
Resistance load
should be the following value.
4 output points/common terminal: 8A or less
Inductive load
OFF ON
ON OFF
150 (5.91")
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
FX
-32ER-ES/UL
2N
16 points
Removable terminal block (M3 screw)
30V DC or less
Mechanical insulation
Supplying power to the relay coil will light the LED indicator lamp on panel.
2A/point
→ For cautions on external wiring, refer to Subsection 12.1.3.
5V DC, 2mA (reference value)
Approx. 10ms
Approx. 10ms
Load
Y
DC power
supply
COM
Fuse
Y
External
power supply
COM
Fuse
A common number applies to the
Unit : mm (inches)
87 (3.43")
15 Input/Output Powered Extension Units
FX
-48ER-ES/UL, FX
2N
24 points
Relay
The total load current per common terminal
should be the following value.
4 output points/common terminal: 8A or less
8 output points/common terminal: 8A or less
80VA
→ For the product life, refer to Subsection 14.4.3.
-
of [COM ].
9 (0.36")
-48ER-DS
2N