LG AUUW09GA0 Engineering Product Data Book page 92

Table of Contents

Advertisement

Single CAC
Outdoor Unit
6. Capacity Tables
6.14 AUUW70LAE [UU70W U34]
Cooling Capacity
 ABNW70GB9A0 [UB70 N94]
Outdoor
Air Temp.
20.0 / 14.0
°CDB
TC
SHC
PI
20.0
13.33 13.15 3.33 16.68 15.47 4.41 19.23 17.79 5.48 21.17 18.95 5.69 23.11 18.62 5.90 24.59 18.40 5.94
25.0
12.60 12.60 3.65 15.96 15.08 4.77 18.51 17.40 5.92 20.45 18.56 6.13 22.39 18.23 6.34 23.86 18.01 6.38
32.0
11.59 11.59 4.17 14.94 14.54 5.29 17.49 16.86 6.53 19.43 18.02 6.74 21.37 17.68 6.95 22.85 17.46 6.99
35.0
11.15 11.15 4.39 14.51 14.31 5.51 17.06 16.62 6.79 19.00 17.78 7.00 20.94 17.45 7.21 22.42 17.23 7.25
40.0
10.43 10.43 4.75 13.78 13.78 5.87 14.71 14.62 5.69 16.44 15.65 5.86 18.17 15.34 6.03 19.49 15.13 6.07
43.0
9.99
9.99
4.97 13.35 13.35 6.09 13.30 13.30 5.03 14.91 14.34 5.18 16.52 14.05 5.33 17.74 13.86 5.36
46.0
9.56
9.56
5.19 12.92 12.92 6.31 11.89 11.89 4.38 13.37 13.00 4.50 14.86 12.74 4.62 15.98 12.57 4.64
48.0
9.27
9.27
5.34 12.63 12.63 6.46 10.95 10.95 3.94 12.35 12.10 4.04 13.75 11.86 4.15 14.81 11.70 4.17
Rate of change in TC and PI due to the indoor unit at standard temperature condition.
ABNW70GB9A0 [UB70 N94]
 3Ø Synchro Equlvalent capacity table
Max Power Input of each model is tabulated below
(Duo)
Model
PI
(Trio)
Model
CT24 NP2(4) * 3
PI
(Quartet)
Model
CT18 NQ2(4) * 4
PI
Note
1. DB : Dry bulb temperature( ), WB : Wet bulb temperature( )
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. For Synchro model operating simultaneously with combinations, The individual capacities of indoor unit are not gived because they are same with the
Single model capacities.
6. Direct interpolation is permissible. Do not extrapolate.
7. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
8. In accordance with the test standard(or nations), the rating will vary slightly.
Indoor Air Temperature : °CDB / °CWB
22.0 / 16.0
25.0 / 18.0
TC
SHC
PI
TC
SHC
Model
Max.
Rated
UT36 NN2 * 2
8.71
CM24 N14 * 3
8.26
CM18 N14 * 4
7.84
27.0 / 19.0
PI
TC
SHC
PI
TC
1.10
1.00
UM36 N24 * 2
8.71
CB24L N32 * 3
8.26
8.26
CB18L N22 * 4
7.84
7.84
Standard Inverter
30.0 / 22.0
32.0 / 24.0
TC
SHC
PI
TC
Correction factor
PI
1.39
1.00
UV36 NK2 * 2
8.71
CV24 NJ2 * 3
8.26
CV18 NJ2 * 4
7.84
SHC
PI
85