Single CAC
Outdoor Unit
7. Capacity Coefficient Factor
7.1 Rate of change in capacity due to the main piping length
 Rate of change in cooling capacity
Piping length(m)
Rate of change in capacity(%)
 Rate of change in heating capacity
Piping length(m)
Rate of change in capacity(%)
7.2 Calculation of actual system capacity
1. Outdoor unit capacity at Ti, To temperature.
Q
[from capacity table]
(Ti, To)
2. Piping correction factor
F
for piping length [from capacity coefficient factor table]
piping
3. Indoor Unit actual capacity
Q
= T
x F
actual
(Ti, To)
piping
5
5.0/7.0 kW
100
8.0 kW
100
10.0 kW
100
5
5.0/7.0 kW
100
8.0 kW
100
10.0 kW
100
10
15
20
99.3
97.9
96.6
99.3
97.9
96.6
99.3
97.9
96.6
10
15
20
99.7
99.2
98.7
99.7
99.2
98.5
99.7
99.2
98.5
Compact Inverter
30
35
40
93.8
-
-
93.8
92.4
-
93.8
92.4
91.1
30
35
40
97.7
-
-
97.7
97.1
-
97.7
97.1
96.6
17