Refrigerant Piping System - LG AUUW09GA0 Engineering Product Data Book

Table of Contents

Advertisement

MULTI/SINGLE CAC

4. Refrigerant piping system

Single type - Synchro
CAUTION
Please check the product type. Piping installation and refrigerant charge varies depending on the type of
product.
For more information, please refer to the installation manual.
When installing the branch pipe, direction and angle of installation is not limited.
Take care so that burrs and foreign material may not enter into the cutting surface when connecting.
Connect remaining those by cutting or direct insertion to the diameter of pipe.
 Refrigerant additional charge calculation method
Liquid Pipe Diameter (mm)
Additional Refrigerant = (L1 - A) x a + (L2 + L3 + L4 + L5) x b
L1 (m) : Installed Branch Piping Length (Outdoor Unit ~ Branching Kit)
L2~L5 (m) : Installed Branch Piping Length (Branching Kit ~ Indoor Unit)
a (g/m) : Additional charging volume for Main Pipe (Outdoor Unit ~ Branching Kit)
b (g/m) : Additional charging volume for Branch Pipe (Branching Kit ~ Indoor Unit)
* Refer to the specifications for detail information of A, a.
* If total additional charge value after calculation comes out to be negative, then do not consider additional charge.
CAUTION
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
10
L2
Indoor Unit
L3
L4
Indoor Unit
L5
Branch
L1
Notes
L1 (m)
L2~L5 (m) : Branch Piping Length (Branching Kit ~ Indoor Unit)
L6 (m)
H1 (m)
H2 (m)
Refer to the specifications of Outdoor Unit for Maximum limit.
Ø 6.35
Ø 9.52
Indoor Unit
Indoor Unit
L6
: Main Piping Length (Outdoor Unit ~ Branching Kit)
: Length Difference (the Nearest Indoor Unit ~ the farthest Indoor Unit)
: Height Difference (Outdoor Unit ~ Indoor Unit)
: Height Difference (Indoor Unit ~ Indoor Unit)
Installation of Outdoor Units
b (g/m)
35
40