9. DUCTING

Good duct design and sizing are essential to every Central Heating system. Use the Product Sizing Guide and
technical data within this manual for the best results and follow these guidelines:
Ductwork should be well insulated and airtight and have a minimum insulation rating of R1.0 (R1.5 in some
areas). Ensure that ducting complies with the Building Code of Australia.
The ducting should be well fastened to pops, BTOs, outlet boots and neck adapters adequately with duct tape,
in accordance with AS 4254, HB 276 and AS5141.
It should also be properly sized, and curves and bends should be smooth enough to ensure that the air flows
through efficiently, quietly and with minimal resistance.
The registers and diffusers should be large enough and of good design. They should minimise noise, while
providing the correct distribution pattern.
The positive return air system should be fitted with a grille large enough to accept the full air capacity of the
system at low noise levels.
If the system uses high level outlets (e.g. ceiling diffusers), then the return air inlet should be at a low level.
Ceiling systems with a high level return air may result in reduced performance.
For SP5 and SP6 heaters, access to the ductwork must be provided for general maintenance and service to the
supply air thermistor sensor.
Note: It is important that the ducting should be well insulated. It is mandatory under building codes to install insulated, fire rated duct.
If a filter is fitted to the return air grille, make sure it is easily accessible for regular cleaning.
Table 7 gives the minimum recommended return air grille sizes for each model heater.
Table 7. Minimum Recommended Return Air Grille Selection
SP521, SP615, SP623
SP521 XA, SP623 XA
SP530, SP630
SP530 XA, SP630 XA
SP535, SP635
Note: Sizes are based on maximum airflow for typical 'egg-crate' grilles. For all other types, refer to the manufacturer's specifications.
Example:
If a grille has a free ventilation opening of 500mm x 800mm, the grille size is 0.5m x 0.8m = 0.4m²
Without a filter, this grille suits the SP530 XA heater, which requires at least 0.38m².
With a filter, this grille suits the SP623 heater, which requires at least 0.39m².
Brivis
Model
Without Filter
Grille Size
Example Size
(m²)
(mm)
0.26
(400x650)
0.28
(400x700)
0.36
(400x900)
0.38
(400x1000)
0.39
(400x1000)
24
With Filter
Grille Size
Example Size
(m²)
(mm)
0.39
(400x1000)
0.42
(400x1050)
0.54
(400x1350)
0.57
(400x1450)
0.58
(400x1450)
Ducted Gas Heater IM