Domestic ventilation unit M Flex Air (Plus)
6.5.3 Data connection
An RS 485 cable must be installed to connect to the heat pump
manager. The plug for connection to the connector panel on
the ventilation unit is included in the scope of supply. It must be
attached to an on site cable - LIYY 3 x 0.34 mm2 is recom-
mended.
Only the end customer menu options level adjustment, filter
reset and information can be accessed in the System M / M Flex
user interface. All other menu options must be set on the venti-
lation controller.
6.6 Vertical wall mounting
(accessory)
6.6.1 Scope of supply
The scope of supply of the accessory includes:
1)
Mounting rail
2)
Unit/mounting rail screws
3)
Set screws
1
2
3
Fig. 6.11:Accessories
www.glendimplex.de
6.6.2 Wall mounting installation
The wall mounting must be installed horizontally. When install-
ing the unit, a vibration decoupling mounting may be necessary
depending on the construction of the wall. This is to be carried
out on site.
HINWEIS
NOTE
Where possible, the device should not be installed on a wall
adjoining a bedroom. Alternatively, a vibration decoupling
mounting should be used.
Fig. 6.12:Wall mounting installation
1)
Attach the mounting rail at the upper threaded inserts on
the rear of the unit
2)
Screw the set screws into the lower threaded inserts on the
rear of the unit
3)
Screw the mounting rail horizontally onto the wall. The in-
stallation materials should be selected according to the na-
ture of the wall
4)
Mount the unit
5)
Align the unit using the set screws
DOK4SVxxDEN · FD 9912