Clean Heat-Exchangers - Buderus Logano plus GB402 Installation And Maintenance Instructions For Contractors

Table of Contents

Advertisement

▶ Undo all 4 screws with sleeve [1] between the mixture manifold and
the carriage.
Fig. 48 Undoing the mixture manifold from the carriage
[1]
Screws with sleeve
▶ Pull out the burner rod together with the mixture manifold.
Fig. 49 Removing the burner
▶ Blow off the burner rods and mixture manifold from the inside and
outside using a reasonable amount of compressed air (max. 3 bar).
If there is heavy contamination, the burner rod can be separated from
the mixture manifold and a blow gun with a long, angled blow pipe can be
used to blow them off from the inside and outside using a reasonable
amount of compressed air (max. 3 bar).
▶ Re-install the burner rod with a new gasket.
Logano plus GB402 – 6 720 820 700 (2018/01)

10.6.2 Clean heat-exchangers

Dry cleaning the heat exchanger
▶ Remove the thermal insulation from the heat exchanger.
Fig. 50 Heat exchanger thermal insulation
6 720 618 585-38.2T
[1]
Clamp
[2]
Thermal insulation
▶ Undo fixing nuts from cleaning covers [1] at the heat exchanger.
▶ Remove the cleaning covers.
Fig. 51 Opening the cleaning covers
[1]
Cleaning cover
▶ Undo the fixing nuts from the top and bottom of the condensate pan
cover.
▶ Removing the cover.
Inspection and servicing
CAUTION: Risk of injury from sharp edges of cleaning
blade!
▶ To avoid injury, wear protective gloves when
cleaning the boiler using cleaning blades
(accessories).
10
37

Advertisement

Table of Contents
loading

Table of Contents