Buderus Logano plus GB402 Installation And Maintenance Instructions For Contractors page 52

Table of Contents

Advertisement

11
Troubleshooting
1)
Type
Display code Fault Code
B
8L
534
V
8P
580
V
8U
581
V
9Y
500
501
502
503
V
CY
566
V
CY
567
V
CO
568
V
CO
569
Table 23 Fault displays
1) V = locking; B = blocking
52
Reason
Description:
No gas pressure
There is no gas
or additional flue
pressure although
gas pressure
solenoid valve 1 should
limiter (pressure
have opened. The
> 7.5 bar) has
burner makes three
responded.
successive attempts at
starting, then it waits
for one hour before
making three more
start attempts.
Solenoid valve 1
The valve test system
leaking
has detected an
unacceptably high
leakage rate on
solenoid valve 1.
Solenoid valve 2
The valve test system
leaking
has detected an
unacceptably high
leakage rate on
solenoid valve 2.
Internal SAFe
Internal SAFe
relay faulty.
electronics faulty.
Return
The control unit
temperature
receives unrealistic
values from the return
< -5 °C
sensor.
(interruption)
Return
The control unit
temperature
receives unrealistic
values from the return
> 130 °C (short
sensor.
circuit)
Water pressure
Water pressure sensor
sensor fault
interruption (voltage >
(cable break).
3.5 V).
Water pressure
Water pressure sensor
sensor fault
short circuit (voltage <
(short circuit).
0.5 V).
Test procedure/cause
Check that the gas isolator is
open.
Check whether there is gas
pressure.
Check whether the flue gas
pressure limiter has responded.
Check electrode.
Check ignition transformer.
Check gas filter for
contamination.
Check the gas valve for
contamination.
Gas filter fitted.
Check the gas valve for
contamination.
Gas filter fitted.
Press "Reset" and wait to see if
the fault has been removed.
Check cabling between SAFe and
return sensor.
Check electrical connection of the
SAFe cable.
Check the resistance values of the
temperature sensor against the
table.
Check voltage at the temperature
sensor terminals inside the SAFe
according to table.
Check cabling between SAFe and
return sensor.
Check electrical connection of the
SAFe cable.
Check the resistance values of the
temperature sensor against the
table.
Check voltage at the temperature
sensor terminals inside the SAFe
according to table.
Check lead to water pressure
sensor.
Check water pressure sensor.
Check lead to water pressure
sensor.
Check water pressure sensor.
Logano plus GB402 – 6 720 820 700 (2018/01)
Corrective measure
Replace the gas valve if
required.
Check the gas pressure.
Reset the flue gas pressure
limiter.
Check the flue gas path for
blockages.
Replace electrode if required.
Replace ignition transformer if
required.
Replace gas filter if required.
Replace the gas valve.
Replace the gas valve.
Replace the SAFe if the fault
persists after "Reset" has been
pressed.
Replace cable if required.
Remedy contact problem if
required.
Replace temperature sensor if
required.
Replace SAFe if resistance
values of the temperature
sensor are correct, but voltage
values are incorrect.
Replace cable if required.
Remedy contact problem if
required.
Replace temperature sensor if
required.
Replace SAFe if resistance
values of the temperature
sensor are correct, but voltage
values are incorrect.
Eliminate any interruption.
Replace water pressure
sensor.
Remedy any short circuit.
Replace water pressure
sensor.