3.2
Refrigeration System Data
Compressor / Motor Assembly Model Number
Electronic Expansion Valve
(EEV) Superheat Evaporator
Economizer Expansion Valve
(EXV) Superheat
Heater Termination Thermo-
stat (HTT)
High Pressure Switch (HPS)
EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal
injury and / or property damage.
Never use air or gas mixtures containing oxygen (O
Charge Only With R-134a: Refrigerant must conform to AHRI Standard 700 specification.
Refrigerant
Charge water-cooled condenser or receiver according to nameplate specifications to ensure
optimal unit performance.
Refrigerant Charge
Fusible Plug
Rupture Disc
Unit Weight
Water Pressure Switch (WPS)
3.3
Electrical Data
Circuit Breaker
Compressor Motor (CP)
Weight (With Oil)
Approved Oil
Oil Charge
Verify at -18°C
(0F) container box
temperature
Verify at -18°C
(0F) container box
temperature
Opens
Closes
Cut-Out
Cut-In
WARNING
!
R-134a
CAUTION
!
Water-Cooled Condenser
Receiver
Melting point
Torque
Bursts at
Torque
Cut-In
Cut-Out
CB-1 (25 amp)
CB-2 (50 amp)
CB-2 (70 amp)
Full Load Amps (FLA)
ZMD26KVE-TFD-272
Uniqema Emkarate RL-32-3MAF
1774 ml (60 ounces)
4.4 to 6.7°C (8 to 12°F)
4.4 to 11.1°C (8 to 20°F)
54° (+/- 3) C = 130° (+/- 5) F
38° (+/- 4) C = 100° (+/- 7) F
25 (+/- 1.0) kg/cm
18 (+/- 0.7) kg/cm
) for leak testing or operating the product.
2
Conforming to AHRI standard 700 specifications.
5.44 kg (12 lbs)
4.99 kg (11 lbs)
99°C = (210°F)
6.2 to 6.9 mkg (45 to 50 ft-lbs)
35 +/- 5% kg/cm
6.2 to 6.9 mkg (45 to 50 ft-lbs)
Refer to unit model number plate.
0.5 +/- 0.2 kg/cm
1.6 +/- 0.4 kg/cm
Trips at 29 amps
Trips at 62.5 amps
Trips at 87.5 amps
13 amps @ 460 VAC
3–7
42.9 kg (95 lb)
2
= 350 (+/- 10) psig
2
= 250 (+/- 10) psig
2
= (500 +/- 5% psig)
2
(7 +/- 3 psig)
2
(22 +/- 5 psig)
T-340