Checklist For Yearly Maintenance Of The Outdoor Unit; About Service Mode Operation; To Use Vacuum Mode; To Recover Refrigerant - Daikin LRMEQ3AY1 Installer And User Reference Manual

Air-cooled refrigeration condensing unit
Table of Contents

Advertisement

11 Troubleshooting

2 Measure the voltage between terminals on the terminal block
for power supply with a tester and confirm that the power supply
is shut off. In addition, measure points as shown in the figure
below, with a tester and confirm that the voltage of the capacitor
in the main circuit is less than 50 V DC.
C+
C–
3 To prevent damaging the PCB, touch a non-coated metal part
to eliminate static electricity before pulling out or plugging in
connectors.
4 Pull out junction connectors for the fan motors in the outdoor
unit before starting service operation on the inverter equipment.
Be careful not to touch the live parts. (If a fan rotates due to
strong wind, it may store electricity in the capacitor or in the
main circuit and cause electric shock.)
Junction connectors
5 After the service is finished, plug the junction connector back in.
Otherwise the malfunction code E7 will be displayed and
normal operation will not be performed.
For details refer to the wiring diagram labelled on the back of the
service cover.
Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Make sure to turn off the main switch and to remove
the fuses from the control circuit located in the outdoor unit.
10.3
Checklist for yearly maintenance
of the outdoor unit
Check the following at least once a year:
▪ Outdoor unit heat exchanger.
The heat exchanger of the outdoor unit can get blocked up due to
dust, dirt, leaves, etc. It is recommended to clean the heat
exchanger yearly. A blocked heat exchanger can lead to too low
pressure or too high pressure leading to worse performance.
10.4

About service mode operation

Refrigerant recovery operation/vacuuming operation is possible by
applying setting [2‑21]. Refer to
page 25
for details how to set mode 2.
When vacuuming/recovery mode is used, check very carefully what
should be vacuumed/recovered before starting. See installation
manual of the indoor unit for more information about vacuuming and
recovery.
10.4.1

To use vacuum mode

1 Turn OFF the external operation switch.
2 Activate setting [2‑21] to start vacuuming mode.
Result: When confirmed, the outdoor unit expansion valves will
fully open. At that moment H1P is lit.
3 Evacuate the system with a vacuum pump.
Installer and user reference guide
30
A1P
A2P
X106A for M1F
X107A for M2F
"7.2  Making field settings"  on
4 Press BS1 to stop vacuuming mode.
10.4.2

To recover refrigerant

This should be done by a refrigerant reclaimer. Follow the same
procedure as for vacuuming method.
NOTICE
Make sure to NOT recover any oil while recovering
refrigerant. Example: By using an oil separator.
11
Troubleshooting
11.1

Overview: Troubleshooting

Before troubleshooting
Carry out a thorough visual inspection of the unit and look for
obvious defects such as loose connections or defective wiring.
11.2

Precautions when troubleshooting

WARNING
▪ When carrying out an inspection on the switch box of
the unit, always make sure that the unit is disconnected
from the mains. Turn off the respective circuit breaker.
▪ When a safety device was activated, stop the unit and
find out why the safety device was activated before
resetting it. NEVER bridge safety devices or change
their values to a value other than the factory default
setting. If you are unable to find the cause of the
problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazard due to the inadvertent resetting of the
thermal cut-out: this appliance must NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
DANGER: RISK OF BURNING
11.3
Solving problems based on error
codes
INFORMATION
If a malfunction occurs, a signal (220-240 V AC) is given to
the error output (X2M/E1/E2), and the H2P LED on the
main PCB is lit.
You can display the error codes of the 3 latest malfunctions by using
the push buttons and 7‑LEDs display (see
components"  on page 
25). Error codes consist of 2 characters
(example: E3).
After solving the problem, reset the malfunction by turning OFF and
ON the external operation switch, and retry operation.
11.3.1
To display the error codes of the latest
malfunctions
#
Action
1
Start from the default
situation.
"7.2.3  Field setting
Display
LRMEQ3+4AY1
Air-cooled refrigeration condensing unit
4P442131-1 – 2016.03

Advertisement