Tripping Limits And Tripping Times - SMA Sunny Boy 6000TL‑US Installation Manual

Pv inverter
Hide thumbs Also See for Sunny Boy 6000TL‑US:
Table of Contents

Advertisement

11  Technical Data
11.8 Tripping Limits and Tripping Times
Nominal
frequency
60 Hz
< 57.0 Hz to 59.8 Hz
(Standard 59.3 Hz)
Voltage
Tripping limit -
tripping voltages
208 V
240 V
Measurement accuracy
• Tripping limit accuracy: ±2 % of nominal grid voltage
• Tripping time accuracy: ±1 % of nominal tripping time
• Tripping frequency accuracy: ±0.05 Hz
86
SB6-11TL-US-IA-en-13
Tripping limit
> 60 5 Hz
< 57.0 Hz
Conductor-
neutral conductor
50%
57.6 to 62.4 V
88%
103.2 to 108.0 V
110%
129.6 to 134.4 V 224.6 to 233.0 V
120%
141.6 to 146.4 V 245.4 to 253.8 V
50%
57.6 to 62.4 V
88%
103.2 to 108.0 V 206.4 to 216.0 V
110%
129.6 to 134.4 V 259.2 to 268.8 V
120%
141.6 to 146.4 V 283.2 to 292.8 V
Tripping frequencies
60.45 Hz to 60.55 Hz
56.95 Hz to 59.85 Hz
(Standard
59.25 Hz to 59.35 Hz)
56.95 Hz to 57.05 Hz
Tripping voltage -
conductor-
conductor
99.8 to 108.2 V
178.9 to 187.2 V
115.2 to 124.8 V
SMA America, LLC
Tripping times
max. 0.1602 s
adjustable,
0.16 s to 300 s
(Standard max. 0.1602 s)
max. 0.1602 s
Tripping times
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
Installation Manual