11  Technical Data

11 Technical Data

11.1 Sunny Boy 6000TL-US
PV Array Connection
Maximum DC power
Maximum DC voltage
Minimum DC voltage at 208 V AC
Minimum DC voltage at 240 V AC
DC nominal voltage at 208 V AC
DC nominal voltage at 240 V AC
DC start voltage
MPP voltage range at 208 V AC
MPP voltage range at 240 V AC
Maximum DC input current at 208 V AC
Maximum DC input current at 240 V AC
Number of MPP trackers
Grid Connection
AC nominal power
Maximum AC power
Reduced power output at 140°F (60°C)
Maximum AC current at 208 V AC
Maximum AC current at 240 V AC
Maximum AC reverse current
Maximum AC fuse size
AC nominal voltage
AC voltage range at 208 V AC
AC voltage range at 240 V AC
AC nominal frequency
AC nominal frequency range
Power factor at nominal power
Total harmonic factor
AC connection/Power Balancing
Ground fault monitoring (R-Iso)
Power consumption nighttime
70
SB6-11TL-US-IA-en-13
SMA America, LLC
6,200 W
600 V
300 V
345 V
345 V
379 V
360 V
300 V to 480 V
345 V to 480 V
21 A
18 A
1 (OptiTrac)
6,000 W
6,000 W
6,000 W
33 A
29 A
0 A
45 A
208 V/240 V
183 V to 229 V
211 V to 264 V
60 Hz
59.3 Hz to 60.5 Hz
1
< 4%
Two Phases / ✓
Yes
≤ 0.25 W