Requirements For The Mounting Location - SMA Sunny Boy 6000TL‑US Installation Manual

Pv inverter
Hide thumbs Also See for Sunny Boy 6000TL‑US:
Table of Contents

Advertisement

4  Mounting
4.2 Requirements for the Mounting Location
Requirements
☐ The installation method and mounting location must be suitable for the weight and dimensions
of the Sunny Boy (see Section 11 "Technical Data", page 70).
☐ Note the dimensions of the DC Disconnect (4.3 "Mounting the DC Disconnect", page 25).
☐ Mount the inverter on a stable surface.
☐ The mounting location must be accessible at all times.
☐ Mount vertically or tilted backward at max. 15°.
☐ The connection area must point downward.
☐ Do not install the inverter tilting forward.
☐ Do not install the inverter horizontally.
☐ Install the inverter at eye level in order to be able to read out the operating state at any time.
☐ The ambient temperature must be in a permissable range ("Technical Data" on page 70).
☐ Do not expose the inverter to direct sunlight.
☐ In the living area, do not mount inverters on a
plasterboard wall or similar wall.
The Sunny Boy may emit noises when in use which
can be regarded as a nuisance.