15.4 Steps For Linear Input Calibration

1. Display ANL1, ANH1, DP:
PV/SV monitor
PV
SV
LCK setting to 1111
PV
SV
SET2_2= 1
open ANL1、ANH1、DP
PV
X
X
X
SV
※ X is the default value which doest not require modification
2. input 4mA and djust ANL1 calibration values:
PV/SV monitor
PV
SV
Adjust ANL1 until
PV show 0
PV
SV
※ ANL1 calibration value of each controller is different from the other
3. input 20mA and djust ANH1 calibration values:
PV/SV monitor
PV
SV
Adjust ANH1 until
PV show 5000
PV
SV
※ ANH1 calibration value of each controller is different from the other
FY operation manual
press
key 3 seconds
press
+
key 3 seconds
if SET2_2 setting finish
press
+
key 3 seconds , return to PV/SV monitor
press
+
key 3 seconds
if ANL1 setting finish
press
+
key 3 seconds , return to PV/SV monitor
press
+
key 3 seconds
if ANH1 setting finish
press
+
key 3 seconds , return to PV/SV monitor
Enter to Level 2
show P1
PV
press
SV
Enter to Level 4
show SET1
PV
press
SV
Enter to Level 3
show INP1
PV
press
SV
Enter to Level 3
show INP1
PV
press
SV
PV
key switching to
display"LCK "
SV
SET2 X is
current value
PV
key switching to
X
X
display"SET2 "
SV
PV
key switching to
display"ANL1 "
SV
PV
key switching to
display"ANH1 "
SV
X
74

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fy600Fy700Fy800Fy900Fa230Fa231

Table of Contents