Modify Input Type : Linear Input (Ma ,V); Fy400~900 & Fu48~96 Hardware - Taie FA Series Operation Manual

Digital pid temperature/process controllers
Hide thumbs Also See for FA Series:
Table of Contents

Advertisement

15. Modify input type : Linear Input (mA ,V)

15.1 FY400~900 & FU48~96 Hardware:
FY900,FY600,FY800
INPUT ( + )
PIN 17
INPUT ( - )
PIN 20
0~20mA (INP1=AN4):(R3 use 100Ω,R5 use 2.4Ω, S3 & S5 SHORT)
4~20mA (INP1=AN5):(R3 use 100Ω,R5 use 2.4Ω, S3 & S5 SHORT)
0 ~ 1V
(INP1=AN4):(R1 use 2KΩ,R4 use 100Ω,S1 & S4 SHORT)
0 ~ 5V (INP1=AN4):(R2 use 10KΩ,R4 use 100Ω,S2 & S4 SHORT)
1 ~ 5V (INP1=AN5):(R2 use 10KΩ,R4 use 100Ω,S2 & S4 SHORT)
0 ~ 10V (INP1=AN4):(R3 use 22KΩ,R4 use 100Ω,S3 & S4 SHORT)
2 ~ 10V (INP1=AN5):(R3 use 22KΩ,R4 use 100Ω,S3 & S4 SHORT)
All manuals and user guides at all-guides.com
FU86,FU96
48
FY700
FY400
FU72
FU48
PIN 11
PIN 7
PIN 14
PIN 10

Hide quick links: