Alarm Action - Taie FY400 Operation Manual

Digital temperature controller
Hide thumbs Also See for FY400:
Table of Contents

Advertisement

12. Alarm Action

Description
The FY/FA series controller can support up to three sets of alarm functions. Each set of alarms has 19 mode.
Users can choose the most suitable alarm mode according to their needs for system protection or application.
Function Diagram
Parameter
Parameter
Symbol
AL1
AL2
AL3
ALD1
ALT1
ALD2
ALT2
ALD3
ALT3
HYSA
SETA
FY operation manual
PV
SV
OUT1
OUT2
AT
AL1
AL2
AL3
MAN
OUT1
0
20
40
60
80
TAIE
Content
Alarm1 set value
Alarm2 set value
Alarm3 set value
Alarm1 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
Alarm1 time setting
0 : Flicker
99.59 : Continued ON
0.01~99.58 : delay time
Time format : min . sec
Alarm2 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
Alarm2 time setting
0 : Flicker
99.59 : Continued ON
0.01~99.58 : delay time
Time format : min . sec
Alarm3 mode selection
(Please refer to Chapter 12.1 Alarm
Mode)
Alarm3 time setting
0 : Flicker
99.59 : Continued ON
0.01~99.58 : delay time
Time format : min . sec
Hysteresis setting for alarm1~3
Alarm special function setting
(Please refer to Chapter 12.2)
Alarm 1
PRO
%
Alarm 2
100
FY900
Alarm 3
Range
MAX
MIN
9999
-1999
9999
-1999
9999
-1999
19
0
99.59
0.00
19
0
99.59
0.00
18
0
99.59
0.00
999.9
-199.9
1111
0000
Default
Level
Display
1.0
Level 1
SET1.3
1.0
Level 1
SET1.4
1.0
Level 1
SET2.1
11
Level 3
SET3.1
99.59
Level 3
SET3.2
11
Level 3
SET3.3
99.59
Level 3
SET3.4
11
Level 3
SET4.1
99.59
Level 3
SET4.2
1.0
Level 3
SET4.3
0000
Level 3
SET5.3
Hide/