15.3 Input modify to Linear (4~20mA)

Plug 2 pcs of Jumper in the right slot as shown

Linear analog signal (4~20mA) calibration flowchart

73
Jumper Position
Start
SET 2_2 = 1
ANL1 = 0
ANH1 = 5FFF
DP = 0000
INP1 = AN4
USPL = 5000
LSPL = 0
Input analog signal 4mA
Adjusts "ANL1" until PV = 0
Input analog signal 20mA
Adjusts "ANH1" until PV = 5000
Input 4mA Check the PV = 0
Input 20mA Check the PV = 5000
NO
OK ?
YES
Repeat step A~E 3~4 times
NO
OK ?
YES
End
Set the range you want
Ex: Low = -10.0, High = 10.0
Set LSPL = -10.0, USPL = 10.0, DP : 000.0
Software Setting
Parameter set as "INP1=AN4"
to display ANL1 & ANH1 & DP
at Input level (level 3)
Step A
Step B
Step C
Step D
Step E