12.1 Alarm Mode

:SV
: Alarm set value
ALDX
Alarm mode
0
No alarm function
Deviation high
1
(With hold action)
Deviation low
2
(With hold action)
Deviation high/low
3
(With hold action)
Band
4
(With hold action)
Process high
5
(With hold action)
Process low
6
(With hold action)
7
Segment execute alarm
8
System error
HBA
(Heater Break Alarm)
9
Single RAMP
59
X:1 / 2 / 3 (There are up to 3 sets of alarms)
Description
Not drive any alarm relays and the corresponding LED lamp.
PV ≥ (SV+ALX) → Alarm ON
Formula
PV ≤ (SV+ALX-HYSA) → Alarm OFF
*
ALX must to be set to a negative value
PV ≤ (SV+ALX) → Alarm ON
Formula
PV ≥ (SV+ALX+HYSA) → Alarm OFF
PV ≥ (SV+ALX) → Alarm ON
PV ≤ (SV-ALX) → Alarm ON
Formula
PV ≥ (SV-ALX+HYSA) → Alarm OFF
PV ≤ (SV+ALX-HYSA) → Alarm OFF
PV ≤ (SV+ALX) → Alarm ON
PV ≥ (SV-ALX) → Alarm ON
Formula
PV > (SV+ALX) → Alarm OFF
PV < (SV-ALX) → Alarm OFF
PV ≥ ALX→ Alarm ON
Formula
PV ≤ (ALX-HYSA) → Alarm OFF
PV ≤ ALX→ Alarm ON
Formula
PV ≥ (ALX+HYSA) → Alarm OFF
When SEG=ALX alarm ON
*
This mode only available in program type controller
The Alert action, when PV displays error message
Activated conditions:
1. Heater current is less the HBAC set value
2. OUT1 manipulated value exceed HBOP set value
3. Conditions of 1 & 2 above are established and continue to
exceed 20 seconds.
*
Please refer to Chapter 11.4
*
This mode only available in ALD1 or ALD2
Please refer to Chapter 11.7
This mode only available in ALD3