14.6 Output Calibration Steps
1. Display CLO1 & CHO1:
PV / SV monitor
PV
SV
LCK setting to 1111
PV
press
SV
SET4_4= 1
open CLO1、CHO1
PV
X
X
X
SV
※ : X is default value which does not need to be modified
2. Adjust CLO1 low-point calibration value :
SV = LSPL
Minimum output
PV
SV
adjust CLO1 until
meter = 4mA
PV
SV
※ : CLO1 calibration value of each controller is different from the other
3. Adjust CHO1 high-point calibration value
SV = USPL
Maximum output
PV
press
SV
adjust CHO1 until
meter = 20mA
PV
SV
※ : CHO1 calibration value of each controller is different from the other
FY operation manual
press
key 3 seconds
+
key 3 seconds
if SET4_4 setting finish
press
+
key 3 seconds , return to PV / SV monitor
press
+
key 3 seconds
if CLO1 setting finish
press
+
key 3 seconds , return to PV / SV monitor
+
key 3 seconds
if CHO1 setting finish
press
+
key 3 seconds , return to PV / SV monitor