Siemens FC2005 Programming Manual page 48

Fire alarm
Table of Contents

Advertisement

Buzzer Base Powering
Speaker Base
Powering
Turn Off
Isolator Support
Multi Critieria Usage
(OOT/OOTC Channel)
Multi Criteria Setting
(OOT/OOTC Channel)
Photoelectric Setting
(OOT/OOTC Channel)
Thermal Alarm Usage
(OOT/OOTC Channel)
Thermal Alarm Setting
(OOT/OOTC Channel)
Silenceable
(output channel)
Silenceable On
Waterflow
(output channel)
HoldThroughReset
(output channel)
Volume
(Pri1/2. AudibleControl)
ToneType
(Pri1/2. AudibleControl)
Silenceable
(Pri1/2. AudibleControl)
Silenceable On
Waterflow
(Pri1/2. AudibleControl)
HoldThroughReset
(Pri1/2. AudibleControl)
FDCIO422
Name
Name Addition
A6V10333724_b_en_--
Programming Manual of FC2005/FC901
Available when "ABHW-4B" is selected for "Audible Base Type":
Detection Line Powered
NAC Powered
AUX/DC Powered (default)
Available when "ABHW-4S" is selected for "Audible Base Type":
NAC Powered
AUX/DC Powered (default)
Bool: True/ False (default)
When set as True, the device should be wired according to the
rules for isolator supported. Otherwise, the panel reports
trouble. When set as False (default), the device should be wired
as polar non-sensitive. Otherwise, the panel reports trouble as
well.
Option 1: ASD (default)
Option 2: Photoelectric (alarm)
Option 3: Off
Set the device application scenario. Users can select one
scenario from the drop-down list.
Only available when "Multi Critieria Usage" is set as "ASD".
Only available when "Multi Critieria Usage" is set to
"Photoelectric(alarm)".
Select one option from the drop-down list.
Option 1: Thermal Evaluation(default)
Option 2: Off
Select an option from the drop down list.
ROR: rate of rise
Bool: True (default) / False
Available when "Silenceable" (output channel) is set as True.
Bool: True (default) / False
Device won't be reset when press Reset button on the panel.
Bool: True / False (default)
Maximum Volume (default)
Medium Volume
Select one tone type from the drop-down list
Bool: True (default) / False
Available when "Silenceable" (output channel) is set as True.
Bool: True (default) / False
Device won't be reset when press Reset button on the panel.
Bool: True / False (default)
Name of the device
Additional description of the device; max. 20 characters