19. HOW TO SET SYSTEM TIMER

Function: This option allows the user to set the following system timer parameters:
Timer
Reset Inhibit
Sets the time the user is prevented form
Time
resetting the system after alarm annunciation.
Sets the time interval at which
Trouble/supervis
trouble/supervisory events are re-annunciated if
ory Remind Time
these events were previously acknowledged. 0
means close this function.
Sets the delay time to submit the "AC fail"
AC Fail Delay
trouble event to remote output (DACT, On-board
common trouble relay output, City tie output)
Set the auto silence timer on or off. If the timer is
on, all the silenceable output will be silenced
Auto Silence On
after the "Auto Silence Time" is expired. If the
timer is off, the auto silence timer is not worked.
Auto Silence
Sets the time the silenceable output will
Time
automatically silence itself after alarm sounding.
Silence Inhibit
Sets the time within which the silenceable output
Time
must be activated.
Sets the time no operation occurs before FACP
Login Time
exits to level 1.
Sets the time no operation or event occurs
LCD ShutDown
before LCD turns off its back light. 0 means
Time
never shut down LCD.
Set if the supervisory event is latched. If it's
latched, the supervisory event can be restored
Supervisory
only when system is reset. If it's not latched, the
Latching
supervisory event can be disappeared as soon
as the signal is out.
Set if the supervisory events can be removed
from event list after it disappears. If it is set as
SUP Self
False, a Supervisory Restoral event will be
Restoring
created and appended in event list on the event
disappears. If it is set as True, the supervisory
even can be disappeared on the signal is out.
Set if the trouble events can be removed from
event list after it disappears. If it is set as False,
Trouble Self
a Trouble Restoral event will be created and
Restoring
appended in event list on the event disappears.
If it is set as True, the trouble even can be
disappeared on the signal is out.
Display Status
Set whether to display Status events on FACP
38|63
Programming Manual of FC2005/FC901
Description
Value Scope
Default
{min:0;max:6;}
{min:0;max:30;}
24
{min:1;max:24;}
24
{True;False;}
True
{min:5;max:30;}
30
{min:0;max:240;}
{min:1;max:30;}
{min:0;max:60;}
60
{True;False;}
False
{True;False;}
True
{True;False;}
True
{True;False;}
True
A6V10333724_b_en_--
Min.
Step
0
1min
1h
1h
-
1min
0
1s
1
1min
1min
-
-
-
-