Siemens FC2005 Programming Manual page 21

Fire alarm
Table of Contents

Advertisement

Steps:
1.
Press "Menu" to display the main menu (Fig. 8-1).
2.
Press "→" to select "Oper" submenu, press "↓" to select
"Quicktest" (Fig. 8-2) and press "OK", then the quick test
configure screen is displayed (Fig. 8-3).
3.
Select "Quick Test Time" and press "OK", then the current setting
is displayed (Fig. 8-4). Enter a new setting and press "OK", then
the setting is finished and system returns to the previous screen.
The other parameters of quick test can be changed the same as
above.
Start quick test:
4.
Press "Menu" to display the "Init. Q.Test" item (Fig. 8-5). Press
"OK" to start the quick test. The system time will display quick
test time and start counting down until "0" is reached(Fig. 8-6).
User can now test the initiating devices.
Stop quick test:
5.
Press "Menu" to display the main menu, press "→" to select
"Oper" submenu, press "↓" to select "Cancel Q. Test" and press
"OK" to stop the quick test (Fig. 8-7). Panel reverts to standby
mode.
Extend quick test:
6.
Press "Menu" to display the main menu, press "→" to select
"Oper" submenu, press "↓" to select "Extend Q. Test" and press
"OK" to extend the quick test time. Quick test will re-start from
the beginning of the setting time.
20|63
Programming Manual of FC2005/FC901
Fig. 8-1
Fig.8-2
Fig.8-3
Fig.8-4
Fig.8-5
Fig.8-6
Fig.8-7
A6V10333724_b_en_--