When inspecting and maintaining the absorption chill-
er-heater, observe the following items:
• Never splash water over the electrical parts in-
stalled to the control panel and absorption chiller-
heater.
• Do not change the set values of the control de-
vices and safety switches without permission.
• Do not turn the internal cycle control valve of the
absorption chiller-heater without permission.
• When replacing the oil in the vacuum pump, be
sure to turn OFF the main circuit breaker (MCB1)
in the control panel.

EXHAUST DUCT INSPECTION

Inspect the exhaust duct periodically to check for a gas
leak. If you smell gas, do not operate the machine or
manipulate the switches until the gas smell vanishes.

VALVE INSPECTION

The chiller-heater is equipped with a refrigerant man-
ual blow valve (V8) that blows refrigerant from the re-
frigerant tank to the absorber directly. See Figure 51
on page 131 , Figure 52 on page 132 ,and Figure 53
on page 133 .
The valve must not be tampered with or have its set-
tings altered. Daily maintenance or inspection is the
only reason to touch the valve.
During service and maintenance work, be
sure to turn OFF the main circuit breaker
(MCB1) and fully close the main valve of
fuel gas line. If not, it may cause electric
shock and burn.
Contact your local Johnson Controls
Service Office for inspection and main-
tenance of the unit. Improper inspection
and maintenance can not only cause a
machine problem but also injure workers.
JOHNSON CONTROLS
SECTION 7 – MAINTENANCE

SOLENOID VALVES

The absorption chiller-heater is equipped with the fol-
lowing solenoid valves.

TABLE 34 - SOLENOID VALVES

Purge solenoid valve (1)
Purge solenoid valve (2)
Refrigerant blow
solenoid valve

PUMP SHUT OFF VALVES

The chiller-heater is equipped with the pump shut off
valves shown in Figure 58 on page 140 . They are
used for inspection of the pumps.
If the absorption chiller-heater is operated with incor-
rect valve settings, the pump may be damaged. Do
NOT tamper with the valves.

AIR PURGE VALVES AND DRAIN VALVES

The chiller-heater is equipped with air purge valves
and drain valves for chilled/hot water and cooling
water. They are used to drain the chilled/hot water,
and cooling water. They also purge air when water is
supplied.

PURGE VALVES

The chiller-heater is equipped with the purging valves
shown in Figure 51 on page 131 , Figure 52 on page
132 , and Figure 52 on page 132 . For operation of
those valves, see Purge Procedure on page 130.
SOLENOID VALVE
SYMBOL
NAME
SV1
SV2
SV3
FUNCTION
Close vacuum pump
piping
Close automatic
refrigerant blow piping
7
129