FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
Scope of Delivery
Johnson Controls scope of delivery for the upper com-
munication system covers the control panels for the
upper communication function. The customer is re-
sponsible to deliver all other related equipment: con-
centrator (HUB), installation, wiring, communication
program for the central monitoring unit, etc. See Table
10 on page 36 for more information.
TABLE 20 - SCOPE OF DELIVERY
ITEM
Control panel with
upper communication
function
Data concentrator
(HUB)
Wiring work for Ethernet
connection
Communication
program for central
monitoring unit
Connection Port for Ethernet Communication
Make sure that the Ethernet cable is plugged into the
correct port on the Control Panel. The Ethernet con-
nection port is located at the bottom left on the back of
the Control Panel.
TABLE 21 - ETHERNET INTERFACE SPECIFICATION
ITEM
Communication format
Connector shape
LED function
JOHNSON CONTROLS
CUSTOMER
X
X
X
10BASE-T/100BASE-TX
RJ-45 type modular jack connector
Active
(Green)
Link
(Green)
JCI
X
Communication protocol: Modbus TCP
Installation and wiring are included
Apply twisted pair cable
See Table 11 on page 38 and Table 12 on
page 39 for the details of the IP address,
function code, communication data address,
etc.
SPECIFICATION
Blink
Data sending/receiving
No light
No data sending/receiving
Blink
Data sending/receiving via
10BASE-T/100BASE-TX
No light
No connection or successor job
failure
SECTION 4 - TECHNICAL DATA
REMARKS
69
4