FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
TABLE 13 - READ COMMAND (CONT.)
15
Chilled/Hot water inlet temp.
16
Chilled/Hot water outlet temp.
17
Refrigerant temp. at evaporator
18
Cooling water inlet temp.
19
Cooling water outlet temp
20
Absorber solution temp.
21
High temperature generator
solution temp.
22
Exhaust gas temp.
23
High temperature generator
pressure
24
Motor opening rate
25
High temperature generator
concentration
26
Purge tank pressure

TABLE 24 - WRITE COMMAND

ITEM
1
Chiller-heater operation signal
2
Chiller-heater stop signal
3
Set point
JOHNSON CONTROLS
12.0
°C
00083
7.0
°C
00085
5.0
°C
00087
32.0
°C
00089
37.0
°C
00091
38.0
°C
00093
145.0
°C
00095
220.0
°C
00097
70.0
kPa
00099
100.0
%
00101
62.0
%
00103
2.0
kPa
00105
ADDRESS
02001
ON at CHILLER-HEATER OPERATION,
PULSE SIGNAL
02002
ON at CHILLER-HEATER STOP, PULSE
SIGNAL
00203
0050~1000 unit, 1 unit=0.1°C
SECTION 4 - TECHNICAL DATA
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~4000 unit, 1 unit=0.1°C
0001~1100 unit, 1 unit=0.1 kPa
0001~1100 unit, 1 unit=0.1%
0001~1100 unit, 1 unit=0.1%
0001~4000 unit, 1 unit=0.1 kPa
CONTENT
4
71