Cable Requirements; Cable Routing - Johnson Controls S300 Series Hardware Installation Manual

Interface control for access and security devices
Hide thumbs Also See for S300 Series:
Table of Contents

Advertisement

S300-DIN-RDR2SA Module

Cable Requirements

Description
RDR2S-A to Power
1
Supply
RDR2S-A to
Controller
RDR2S-A to
RDR2S
Door Contact
Door Strike and
Shunt
Request to Exit
2
Reader Power
Reader
2
Data0/Data1
General Purpose
Input
General Purpose
Output
1
When wiring more than one RDR2S-A, use the same type of hook-up wire and
communications wire to connect subsequent modules.
2
Refer to reader manufacturer's recommendations when using UL-listed readers. In the
absence of other recommendations, consider these cable specifications taking into
account the number of conductors that will actually be needed for installation.

Cable Routing

The cables should run in grounded conduit or at least two feet from AC power,
fluorescent lights, or other high energy sources.
All data cables should be physically separated from power lines. If
!
conduit is used, do not run data cables in the same conduit as power
cables or certain door strike cables, e.g. strike voltage greater that 42V
CAUTION
or Magnetic door locks without EMI suppression.
24-10239-472 Rev. A
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2007 Johnson Controls, Inc.
Recommended Cable Type
Listed, 18 AWG, hook-up wire
Listed, 18 AWG, 1 twisted pair
Listed, 18 AWG, 1 twisted pair
Belden 8442, 1 twisted,
unshielded pair, 22 AWG
Belden 9740, 1 twisted,
unshielded pair, 18 AWG
Belden 8442, 1 twisted,
unshielded pair, 22 AWG
Belden 9740, 1 twisted,
unshielded pair, 18 AWG
Belden 9744, 2 twisted,
unshielded pair, 22 AWG
Belden 8442, 1 twisted,
unshielded pair, 22 AWG to each
detector
Belden 9740, 1 twisted,
unshielded pair, 18 AWG to each
relay
Hardware Installation
Maximum Segment Length
Wire should fit within the
enclosure.
4000 feet (1219 m) maximum. All
RDR2S-A modules connected to
a single controller must be within
4000 feet of the controller.
4000 feet (1219 m) maximum
500 ft. (152 m)
Depends on power requirements
of the door strike. Voltage to the
strike must not be reduced more
than 10% over the 18 AWG wire,
measured when energized.
500 feet (152 m)
Refer to reader manufacturer's
specification for power
requirements.
500 ft. (152 m). Refer to reader
manufacturer's specification for
data requirements.
500 feet (152 m)
Depends on load.
11