Figure 32. Side Wall Venting, Single Unit - Calcana CAL Series Installation, Operation, Service, And Parts Manual

Table of Contents

Advertisement

CAL-SERIES
ALTERNATIVELY, for models CAL-40A (ALL) CAL-50A (ALL) and CAL-75A (ALL) installer can use material
equal to Calcana 3" x 16 gauge sidewall vent kit PIN#800208, c/w 4" x 3" 16 gauge reducer.
NOTE: MAKE SURE THAT ALL FLUE/EXHAUST JOINTS ARE SEALED. USE ONLY SUITABLE PRODUCTS EQUAL TO GENERAL ELECTRIC
RTU 106 OR PERMATEX FORM A GASKET RED HIGH TEMPERATURE SILICONE ADHESIVE SEALANT. (NOT SUPPLIED)
NOTE: VENT PIPE CAN BE TRIMMED IF NEEDED. CUT EXCESS MATERIAL AS REQUIRED. MAINTAIN 6" (16 cm) CLEARANCE TO
COMBUSTIBLES. SEAL ALL JOINTS WITH HIGH TEMPERATURE SILICON (SEE PAGE 36).
NOTE: Maximum length is 25 feet including, two (2) 90° elbows, deduct 10' for every additional 90° elbow
and 5' for every 45° elbow.

Figure 32. SIDE WALL VENTING, SINGLE UNIT

39