Clearance To Combustibles For Space Heating And Brooder Installation; Figure 3. Vented Clearances - Calcana CAL Series Installation, Operation, Service, And Parts Manual

Table of Contents

Advertisement

CAL-SERIES
VENTED
6.1

CLEARANCE TO COMBUSTIBLES FOR SPACE HEATING AND BROODER INSTALLATION

IN THE USA: Residential Garage heater installations with less than an 8' (2.44 m) clearance from the bottom
of the tube to the floor require the installation of the Protective Screen Kit PIN#3900212 (see page 20 for
details) The minimum floor clearance is 6' (1.83 m) from the floor to the bottom of the reflector.
IN CANADA: Residential Garage heater installations with less than an 7' (2.14 m) clearance from the bottom
of the tube to the floor require the installation of the Protective Screen Kit PIN#3900212 (see page 20 for
details) The minimum floor clearance is 6' (1.83 m) from the floor to the bottom of the reflector.
WARNING: I
n all situations, clearances to combustibles must be maintained. Minimum clearance
from heater must be maintained from vehicles parked below heater. The posting of signs may be
required in storage areas referring to clearances to combustibles to the heater and/or limiting the
stacking height of stored Items near the heater specifying a maximum height. Clearances are not for use
in four (4) sided enclosures. Certain materials or items, when stored under the heater, will be subjected
to radiant heat and could be seriously damaged.
WARNING
: The stated clearance to combustibles represents a surface temperature of 90°F (32°C)
above room temperature. Building material with low heat tolerance (such as plastics, vinyl siding, canvas,
tri-ply, etc...) may be subject to degradation at lower temperatures. It is the installer's responsibility to
assure that adjacent materials are protected from degradation. When in doubt, check heat tolerance of
building material(s) with their manufacturer.

Figure 3. VENTED CLEARANCES