6.3.1 Panel Key-switch

Table 6.2 shows the function of the key-switch on the graphic display panel.
No.
Name
OPERATION
LOCK

6.3.2 Panel Keys

Table 6.3 shows the functions of the keys on the graphic display panel.
When operating the keys on the graphic display panel, hold down the key for
at least 0.5 second.
When operating the reset key on the graphic display panel, hold down the
NOTES
key for at least 5 seconds.
The operation may not be performed if the key is held down for shorter periods
of time.
Table 6.3
No.
Name
RUN
STOP
UPS
BYPASS
Table 6.2
Key-switch Function
Function
Setting this key-switch to the "OPERATION"
side enables operation using the buttons on
the panel; setting it to the "OPERATION
INHIBITED" side prevents operation. When
the switch is set to the "OPERATION
INHIBITED" side, buttons
Table 6.3 are inoperative and pressing them
has no effect upon the operation of the UPS.
LCD scroll buttons
and
regardless of the position of this switch.
Key Functions (For HS or AHH individual battery systems)
Function
Starts up the UPS.
Stops the UPS.
Changes to UPS power
supply
Changes to bypass power
supply
- 15 -
6 F 3 H 1 0 0 1
Remarks
Normally setting the
switch to the
OPERATION INHIBITED"
prevents operational
errors. The key can be
-
and
in
removed when it is set to
the "OPERATION
INHIBITED" position; it
are effective
cannot be removed when
the switch is set to the
"OPERATION" position.
Remarks
The UPS starts up when this key is
pressed after the required operational
preparations are complete.
Pressing this key during operation
prepares the UPS to be stopped with
the required procedure.*
Pressing this key during UPS operation
when bypass power is being supplied
changes it to UPS power.
Pressing this key during UPS operation
when the bypass is normal changes it to
bypass power.