9.2 LCD Failure Displays

When a failure occurs, a screen such as that shown in Figure 9.1, and when a warning
occurs, a screen such as that shown in Figure 9.2, will be displayed on the LCD.
FAULT STOP
SERVICEMAN CALL
UPS SUPPLY
AC-VO
AC- I O
When a warning (a limitation on operation or a guidance failure) occurs, "ALARM" will be displayed in the upper
right of the LCD.
Select the desired warning data with the scroll buttons.
Detailed warning data can be displayed.

9.2.1 Failure Data Screen

This screen appears when a trip error is detected.
Up to 10 screens of failure data can be displayed.
Figure 9.3 and Table 9.1 show a sample screen and describe the data shown in the screen.
No.
Name
No.
Failure
Message
Time
Scroll indicator
Select the desired failure data with the scroll buttons.
Detailed failure data can be displayed.
Figure 9.1
ALARM
200[V]
50[
]
%
Figure 9.2
FAULT
1 52R TRIP
98-09-09 08:05:30
↓ANOTHER ITEM
Figure 9.3
Sample Failure Data Screen
Table 9.1
Failure Data Screen Descriptions
Description
The number of the message in the order that it was detected (1 - 10).
(Up to 10 screens of failure data can be displayed.)
Shows the nature of the failure. For details, see Section 9.2.3
"Failure Messages".
The date and time (in 24-hour time) that the failure was detected.
Indicates whether there is a failure screen before or after this screen.
• ↑ indicates there is a failure screen before this screen.
• ↓ indicates there is a failure screen after this screen.
• ↑↓ indicates there are failure screens both before and after this
screen.
- 43 -
FAULT
1 52R TRIP
98-09-09 08:05:30
↓ANOTHER ITEM
Failure Display
WARNING
1 72B MIS OPE
98-09-09 08:05:30
↓ANOTHER ITEM
Warning Display